TOPSAFE
KSVR/VS Vacuum Relief Valve
Vacuum relief valve to API 2000, protecting a tank against under pressure only. The KSVR is weight loaded from −20 to −700 mmW.C, the KSVS spring loaded from −700 to −7,000 mmW.C.
- Type
- Vacuum relief only
- Design code
- API 2000
- Setting range (KSVR, weight loaded)
- −20 mmW.C minimum to −700 mmW.C maximum
- Setting range (KSVS, spring loaded)
- −700 mmW.C minimum to −7,000 mmW.C maximum
- Size range
- 50 mm to 300 mm
- Connection
- ANSI 150lb FF flange as standard; different connections available on request
- Body materials
- Aluminium, carbon steel, 304SS, 316SS, with various trims
KSVR dimensions (weight loaded type)
geser →| Size | N.D | C | APP. L | ABT. H |
|---|---|---|---|---|
| 2" | 50 | 140 | 310 | 123 |
| 3" | 80 | 206 | 460 | 141 |
| 4" | 100 | 225 | 480 | 152 |
| 6" | 150 | 255 | 563 | 184 |
| 8" | 200 | 320 | 690 | 213 |
| 10" | 250 | 370 | 800 | 244 |
| 12" | 300 | 400 | 860 | 270 |
Unit = mm. Standard connection: ANSI 150LB FF flange. JIS or different sizes available on request.
Angka sesuai publikasi prinsipal. Konfirmasikan pilihan akhir dengan lembar data terbaru sebelum memesan.
Typical response within one working day. Cut-to-length and site support available.
Produk terkait
All tank accessories →
TOPSAFE
KSBB/BS Pressure Vacuum Relief Valve
FM approved tank breather valve venting to atmosphere.

TOPSAFE
KSBG/GS Pressure Vacuum Relief Valve
Tank breather valve for pipe away applications.

TOPSAFE
KSBBFI/BSF Breather Valve with Flame Arrester
Combined breather valve and flame arrester in one body.

TOPSAFE
KSEP Emergency Vent Cover
Emergency pressure relief vent cover for fire exposure venting.