
TOPSAFE
TIDF Flame Arrester (Gas Group IIB)
The only arrester in this range certified for the more reactive NEC group C / IEC IIB gases, and the only one to EN ISO 16852 and the IMO MSC.1/Circ.1324 and 1325 marine circulars. Offered in Ni-Al bronze and Hastelloy-C as well as steel.
- Type
- Described on the datasheet as an in-line deflagration arrester in its title, as detonation proof in its section heading, and as end of line in its introduction
- Design codes
- IMO MSC/Circ.677; MSC.1/Circ.1324; MSC.1/Circ.1325; EN ISO 16852
- Compliance
- Meets USCG, IMO MSC/Circ.677 and EN ISO 16852 requirements
- Gas group
- Standard flame cell suitable for NEC group C or IEC IIB gases; cells for other gas groups available as additional extras
- Endurance burn
- Designed to protect against continuous burning against the 316LSS flame cell for a specific period
- Flow
- Bi-directional
- Installation
- Horizontal or vertical
- Housing materials
- Carbon steel (epoxy coated), 304SS or 316SS housing with 316LSS flame cells
- Materials of construction
- Body: carbon steel (spec 1), stainless steel (spec 2), Ni-Al bronze (spec 3), Hastelloy-C (spec 4). Element assembly: stainless and high grade steel or alloy. Gasket: non-asbestos, graphite, Teflon. Stud bolt/nut: A193-B8 / A194-8 standard, high grade steel or alloy
- Connection
- Standard flanges ANSI 150lb; other connections available upon request
TIDF dimensions
滑动 →| Size | N.D | Ø D | APPX. L |
|---|---|---|---|
| 2" | 50 | 220 | 295 |
| 3" | 100 | 280 | 350 |
| 4" | 125 | 320 | 360 |
| 6" | 150 | 445 | 425 |
| 8" | 200 | 545 | 450 |
| 10" | 250 | 650 | 475 |
| 12" | 300 | 750 | 530 |
Unit = mm. Reproduced as printed: the datasheet gives 3" as N.D 100 and 4" as N.D 125, where the other arresters in this range use 80 and 100.
数据以厂商公布为准。最终选型请在订购前对照当前数据表确认。
Typical response within one working day. Cut-to-length and site support available.

TOPSAFE
KSBB/BS Pressure Vacuum Relief Valve
FM approved tank breather valve venting to atmosphere.

TOPSAFE
KSBG/GS Pressure Vacuum Relief Valve
Tank breather valve for pipe away applications.

TOPSAFE
KSVR/VS Vacuum Relief Valve
Vacuum-only relief valve for storage tank protection.

TOPSAFE
KSBBFI/BSF Breather Valve with Flame Arrester
Combined breather valve and flame arrester in one body.
