Skip to content
PT Hiram Kokoh Mulia
KSFH In-Line Flame Arrester
TOPSAFE

KSFH In-Line Flame Arrester

In-line flame arrester to API 2000, BS 7244 and EN 12874, and Factory Mutual approved. Its element can be removed without forcing the pipework apart, which the other in-line models do not offer.

Type
Explosion and deflagration proof, in-line
Design codes
API 2000; BS 7244; EN 12874
Approval
FM (Factory Mutual) approved
Compliance
Meets USCG, IMO MSC/Circ.677 and EN 12874 requirements
Gas group
Standard flame cell suitable for NEC group D or IEC IIA gases; cells for other gas groups available as additional extras
Flame cell
316L stainless steel crimped metal ribbon
Flow
Bi-directional flow and flame arresting
Installation
Vertical or horizontal. No need to force out pipe-lines to remove the element
Deflagration class
Heat transfer characteristics designed for slow moving flames and low medium pressure fronts (low to medium deflagration)
Housing materials
Aluminium, nodular iron, cast steel, 304SS, 316SS, 316LSS. Iron and steel housings supplied epoxy coated
Materials of construction
Body: C.I standard; cast C.S or S.S & AL special. Element ring: C.S or S.S. Element: aluminium or stainless steel. Coating: in-out side epoxy 250 micron except for S.S and AL parts

Typical response within one working day. Cut-to-length and site support available.